Kenmore is a popular appliance brand commonly sold by Sears, but Sears does not manufacture any of the appliances themselves. Instead, they source that out and have other manufacturers make their appliances for them. Kenmore refrigerators are made by a variety of different manufacturers including LG, Electrolux, GE, and Whirlpool.

115 Soru Tümünü görüntüle

I cannot get the refrigerator to go less that 50 degrees?

I have a side by side kenmore and the freezer is -10 and the fan condenser fan is new. No build up of ice, the coils are clean, new control board, new thermostat for the refrigerator and for the freezer. I cannot get the refrigerator to go less that 50 degrees? I am stumped> This is a tough one sense it seems to be working fine. Oh i charged the compressor as well. Now the freezer gets -10 . Is there something that i am missing?

Yanıtlandı! Cevabı görüntüle Ben de bu sorunu yaşıyorum

Bu iyi bir soru mu?

Puan 0
Yorum Ekle

2 Cevap

Filtre ölçütü:
Seçilen Çözüm

Wow! You’ve replaced almost every part. This is either a problem with air flow or refrigerant . You’ll need to unplug refrigerator and remove the panel inside the freezer to expose the evaporator coils. If the evap coils have ice built up all over them, the problem is in the defrost circuit. If there is ice on part of the coils, there’s a problem in the sealed system. Where the refrigerant lines come through the wall at the evaporator, if you notice a clump of ice on the tubing near the wall then you have a sealed system problem. The coils should have no ice

Next you need to take the rear panel off to access the condenser fan motor then plug in the refer. You need to watch the evap coils you’ll hear the compressor turn on and both fams should be running while compressor is running . Watch the evaporator coils and time how long it takes for all the evap coils to have frost on them. If it’s longer than 10 min that’s a seal system problem. If all the evap coils have an even frost pattern all over them within a few minutes, than the sealed system is fine. Next, check the evap fan blade is turning proper Check for air loss through torn or damaged door gaskets. If all is fine then shut the doors and allow 48 hrs for the refer reaches set temperature.

I’m curious to know if you ran a vscum on the system befor you charged and for how long. How much refrigerant did you add and did you repair the leak.?

Bu yanıt yardımcı oldu mu?

Puan 3
Yorum Ekle
En Yararlı Yanıt

Damper Control Assembly

The air damper control opens and closes to let the proper amount of cold air into the refrigerator compartment. If the damper does not open properly, it won’t let enough cold air into the refrigerator. Check the damper control to determine if it is broken or stuck closed.

Bu yanıt yardımcı oldu mu?