The APC RS 1000 is an uninterruptible power supply capable of delivering 600 Watts.

6 Soru Tümünü görüntüle

Overload alarm lights and sound

My ups, after 5 years of continuous operation shows the overload's light .

I unplugged the PC and I replaced the battery but I have not solved the problem.

Then I opened it to see if there are components that are burned or leak but nothing.

To be sure I replaced the cooling fan but nothing has changed.

Can anyone give me some tips?

Thank you very much.

Yanıtlandı! Cevabı görüntüle Ben de bu sorunu yaşıyorum

Bu iyi bir soru mu?

Puan 5
1 Yorum

Hi, i had the same problem twice...!!!

My battery was ok, everything was ok but

the beep keep going on, for overload...

Both times i fixed doing these steps...

- Turn off the unit

- Flip over the unit

- Open the battery-cap and turn the power on

- Green Light is flashing

- Try Now (with the green light flashing) to disconnect the battery...

- Now it should be ON with the Empty battery light on (Red light)

- Connect again the battery as it is...

Now it should be ok...!!!

Good Luck...

tarafından

Yorum Ekle

5 Cevap

Filtre ölçütü:
Seçilen Çözüm

Thanks to all. I have not solved the problem. I replaced the old ups with a new one.

Bu yanıt yardımcı oldu mu?

Puan 2
Yorum Ekle
En Yararlı Yanıt

Roberto, If it alarms, even with nothing plugged in, then it is possible that one of the MOSFET on your mainboard has failed.

Bu yanıt yardımcı oldu mu?

Puan 4

2 Yorum:

metal–oxide–semiconductor field-effect transistor (MOSFET)

http://en.wikipedia.org/wiki/MOSFET

tarafından

Did you solve the problem? Same problem here, 4 years later..

daigoph@gmail.com

tarafından

Yorum Ekle

Hi, i had the same problem twice...!!!

My battery was ok, everything was ok but

the beep keep going on, for overload...

Both times i fixed doing these steps...

- Turn off the unit

- Flip over the unit

- Open the battery-cap and turn the power on

- Green Light is flashing

- Try Now (with the green light flashing) to disconnect the battery...

- Now it should be ON with the Empty battery light on (Red light)

- Connect again the battery as it is...

Now it should be ok...!!!

Good Luck...

Bu yanıt yardımcı oldu mu?

Puan 2

1 Yorum:

Thank you but I replaced the old ups with a new one. Yours sincerely.

tarafından

Yorum Ekle

I too facing the same problem....battery charging process is fine...but when i turn on the inverter it trips and shows overload and keep continuosly beep beeps....pls help me to solve this problem....i expecting board level service suggestions ...thank you

Bu yanıt yardımcı oldu mu?

Puan 1
Yorum Ekle

My problem solved with removing the all cables also power cable wait 5 minute & connect cable again it's working.